Transmission Line Series

XBTOM series On-Line Transformer Gas Analyzer

Our Products Xibang XBTOM series On-Line Transformer Gas Analyzer accurate insight of the condition of transformers is essential for all electrical networks and on-line monitoring of critical transformers has become increasingly important.The knowledge

/uploadfile/2019/08/06/20190806152127sbD9cq.jpg

Our Products

Xibang XBTOM series On-Line Transformer Gas Analyzer accurate insight of the condition of transformers is essential for all electrical networks and on-line monitoring of critical transformers has become increasingly important.The knowledge gained from closely monitoring expensive transformers can maximize its longevity and avoid expensive failures.

XBTOM series implement detect three kinds of micro characteristic of gas and water on line for transformer oil successfully.it can be installed at the scene of the transformer directly.Sampling automatic,detection of oil gas and water directly.

Main Application

Test equipment for analysis the dissolved gas in transformer oil.

Features

  1. Fast measuring in the field: within 20 minutes ,3 key fault gases and moisture can be read
  2. No consumables: Pure physical photo-acoustic spectroscopy technology,The consumables of calibration gas and carry gas are needless.
  3. Moisture in the oil: The concentration of moisture in the oil can be given during the same one test.accuracy ±1ppm.
  4. Simple:Step-by-step software guides and touch screen,the user pass through the procedure.
  5. Reliable: Engineered design provide inherent reliability and high accuracy
  6. PC communication: PC software allows downloading ,trending and analysis of results
  7. Sample Period: The sample is adjustable and the minimum period<1hour.
  8. Reliable Gas Extraction: No use of membranes or vacuum extraction.

 

 

Technical parameter

Gas

Range(ppm)

Resolution

HYDROGEN(H2)

5.0~5000.0

2ppm

CARBON MONOXIDE(CO)

1.0~50,000.0

2ppm

ACETYLENE(C2H2)

0.5~50,000.0

0.1ppm

WATER(H2O)

>5ppm

2ppm NA

 

 

 

 

 

 

 

 

 

Accuracy or tolerance

When valve

Environment temperature

-40~55℃

Oil Temperature

-40~110℃

Humidity

10~100%RH,without condensation

Oil pressure

While running,0~3bar(0~45psi);other,-1~6bar(-15~87psi)

Communication

USB,RS232,RS485,Modem

Power

90~250VAC,47~63Hz,150W

Alarm output

5A/250VAC;5A/30VDC

Sampling period

1~24Hours

Dimension

800*700*500mm

Weight

20kg